ControlForge Timers, Counters & Function Blocks Guide

James M. Belcher Founder, JMB Technical Services LLC April 2026 | ControlForge v1.0.535


1. Overview​

ControlForge implements 14 IEC 61131-3 standard function blocks. Unlike plain functions, function blocks retain state between scan cycles — a timer remembers how long it has been running, a counter remembers its count, a PID controller remembers its integral term.

CategoryFunction BlocksDescription
TimersTON, TOF, TP, RTOTime-based delays, pulses, and accumulation
CountersCTU, CTD, CTUDEvent counting (up, down, bidirectional)
BistablesSR, RSSet/reset latches with priority control
Edge TriggersR_TRIG, F_TRIGRising and falling edge detection
PID ControllersPID, PIDEProportional-Integral-Derivative feedback control

How Function Blocks Work in ST​

Function blocks are declared as variables, then called with named parameters:

PROGRAM POU_Example
VAR
myTimer : TON; (* Declare instance *)
startButton : BOOL;
output : BOOL;
END_VAR

myTimer(IN := startButton, PT := T#5s); (* Call with inputs *)
output := myTimer.Q; (* Read outputs *)
END_PROGRAM

Each instance maintains its own state. You can have multiple instances of the same type:

VAR
pumpDelay : TON;
fanDelay : TON;
alarmDelay : TON;
END_VAR

2. Timers​

2.1 TON — Timer On-Delay​

Output Q goes TRUE after IN has been TRUE continuously for PT duration. If IN goes FALSE before PT expires, the timer resets.

VAR
startDelay : TON;
END_VAR

startDelay(IN := startButton, PT := T#3s);

IF startDelay.Q THEN
(* Button held for 3 seconds — start motor *)
motor := TRUE;
END_IF;

Inputs:

ParameterTypeDescription
INBOOLEnable input — timer runs while TRUE
PTTIMEPreset time (e.g., T#3s, T#500ms, T#1h30m)
RBOOLReset — clears elapsed time and output

Outputs:

ParameterTypeDescription
QBOOLOutput — TRUE when elapsed >= PT
ETTIMEElapsed time (capped at PT)
DNBOOLDone — TRUE when timing complete
TTBOOLTimer Timing — TRUE while actively counting
ENBOOLEnabled — mirrors IN

Timing Diagram:

IN: ──┐ ┌──────────────────────┐ ┌───
└─────┘ └─────┘
PT: ======== (3 seconds)

Q: ─────────────────┐ ┌─────────
└─────────────┘
<--- 3s --->
IN went FALSE Q stays FALSE
before PT, until IN has been
timer reset TRUE for full PT

2.2 TOF — Timer Off-Delay​

Output Q goes TRUE immediately when IN goes TRUE. When IN goes FALSE, Q stays TRUE for PT duration before going FALSE.

VAR
coolDown : TOF;
END_VAR

coolDown(IN := runCommand, PT := T#10s);

(* Fan keeps running 10 seconds after run command stops *)
fan := coolDown.Q;

Inputs:

ParameterTypeDescription
INBOOLEnable input
PTTIMEOff-delay duration
RBOOLReset

Outputs: Same as TON (Q, ET, DN, TT, EN).

Timing Diagram:

IN: ──┐ ┌────────────┐ ┌───
└─────┘ └─────┘

Q: ──┐ ┌────────────┐ ┌───
└─────┘ └───────────┘
<-- 10s -->
Q holds TRUE
after IN falls

2.3 TP — Timer Pulse​

Generates a fixed-width pulse on the rising edge of IN. Not retriggerable — if IN pulses again during an active pulse, it is ignored.

VAR
oneShot : TP;
END_VAR

oneShot(IN := trigger, PT := T#200ms);

(* 200ms pulse on every rising edge of trigger *)
solenoid := oneShot.Q;

Inputs:

ParameterTypeDescription
INBOOLTrigger input (rising edge starts pulse)
PTTIMEPulse width

Outputs: Same as TON (Q, ET, DN, TT, EN).

Timing Diagram:

IN: ──┐ ┌──┐ ┌──┐
└─┘ └─────┘ └───
^ignored (pulse active)

Q: ──┐ ┌──────────┐
└────────────────┘ └───
<---- 200ms ----> <-200ms->

2.4 RTO — Retentive Timer On-Delay​

Accumulates time while IN is TRUE. Unlike TON, it does not reset when IN goes FALSE — accumulated time is retained. Only an explicit R (reset) input clears the timer.

VAR
runHours : RTO;
totalRuntime : TIME;
END_VAR

runHours(IN := motorRunning, PT := T#8h, R := resetBtn);

totalRuntime := runHours.ET;

IF runHours.Q THEN
(* Motor has accumulated 8 hours of runtime — schedule maintenance *)
maintenanceDue := TRUE;
END_IF;

Inputs:

ParameterTypeDescription
INBOOLEnable — accumulates time while TRUE
PTTIMEPreset time (total accumulation target)
RBOOLReset — clears accumulated time and output

Outputs: Same as TON (Q, ET, DN, TT, EN).

Timing Diagram:

IN: ──┐ ┌──┐ ┌──────────────
└─────┘ └─────┘

ET: 0 2s 2s 4s 4s 6s 8s...
^retained ^retained
when IN when IN
goes FALSE goes FALSE

Q: ──────────────────────────┐
└── (Q stays TRUE until R)
ET >= PT

3. Counters​

3.1 CTU — Count Up​

Increments CV on each rising edge of CU. Q becomes TRUE when CV reaches PV.

VAR
partCount : CTU;
END_VAR

partCount(CU := proxSensor, PV := 100, R := resetBtn);

IF partCount.Q THEN
(* 100 parts counted — signal batch complete *)
batchDone := TRUE;
END_IF;

currentCount := partCount.CV;

Inputs:

ParameterTypeDescription
CUBOOLCount Up — rising edge increments CV
PVINTPreset value (target count)
RBOOLReset — sets CV to 0
LDBOOLLoad — loads PV into CV

Outputs:

ParameterTypeDescription
QBOOLOutput — TRUE when CV >= PV
CVINTCurrent count value

3.2 CTD — Count Down​

Decrements CV on each rising edge of CD. Q becomes TRUE when CV reaches 0.

VAR
remaining : CTD;
END_VAR

remaining(CD := dispenseSensor, PV := 50, LD := loadBtn);

IF remaining.Q THEN
(* All items dispensed *)
hopperEmpty := TRUE;
END_IF;

itemsLeft := remaining.CV;

Inputs:

ParameterTypeDescription
CDBOOLCount Down — rising edge decrements CV
PVINTPreset value (loaded by LD)
RBOOLReset — sets CV to 0
LDBOOLLoad — loads PV into CV

Outputs:

ParameterTypeDescription
QBOOLOutput — TRUE when CV <= 0
CVINTCurrent count value

3.3 CTUD — Count Up/Down​

Bidirectional counter with separate up and down inputs.

VAR
position : CTUD;
END_VAR

position(CU := forwardPulse, CD := reversePulse, PV := 1000, R := homeBtn);

atUpperLimit := position.QU; (* CV >= 1000 *)
atLowerLimit := position.QD; (* CV <= 0 *)
currentPos := position.CV;

Inputs:

ParameterTypeDescription
CUBOOLCount Up — rising edge increments CV
CDBOOLCount Down — rising edge decrements CV
PVINTPreset value (upper threshold)
RBOOLReset — sets CV to 0
LDBOOLLoad — loads PV into CV

Outputs:

ParameterTypeDescription
QUBOOLUpper limit — TRUE when CV >= PV
QDBOOLLower limit — TRUE when CV <= 0
CVINTCurrent count value

4. Bistables (Latches)​

4.1 SR — Set-Reset (Set Dominant)​

When both S1 and R are TRUE, Set wins — Q1 stays TRUE.

VAR
latch : SR;
END_VAR

latch(S1 := startBtn, R := stopBtn);
motorEnabled := latch.Q1;
InputTypeDescription
S1BOOLSet (dominant)
RBOOLReset
OutputTypeDescription
Q1BOOLLatched output (retained)

Logic: Q1 := S1 OR (NOT R AND Q1)


4.2 RS — Reset-Set (Reset Dominant)​

When both S and R1 are TRUE, Reset wins — Q1 goes FALSE. Safer for emergency stop circuits.

VAR
safeLatch : RS;
END_VAR

safeLatch(S := runPermit, R1 := eStop);
motorAllowed := safeLatch.Q1;
InputTypeDescription
SBOOLSet
R1BOOLReset (dominant)
OutputTypeDescription
Q1BOOLLatched output (retained)

Logic: Q1 := NOT R1 AND (S OR Q1)

Safety: Use RS (reset-dominant) for safety-critical latches. An E-stop should always be able to override a run command, even if both signals are active simultaneously.


5. Edge Triggers​

5.1 R_TRIG — Rising Edge Detector​

Output Q is TRUE for exactly one scan when CLK transitions from FALSE to TRUE.

VAR
riseDetect : R_TRIG;
END_VAR

riseDetect(CLK := inputSignal);

IF riseDetect.Q THEN
(* Rising edge detected — execute once *)
batchCount := batchCount + 1;
END_IF;
InputTypeDescription
CLKBOOLSignal to monitor
OutputTypeDescription
QBOOLTRUE for one scan on rising edge

5.2 F_TRIG — Falling Edge Detector​

Output Q is TRUE for exactly one scan when CLK transitions from TRUE to FALSE.

VAR
fallDetect : F_TRIG;
END_VAR

fallDetect(CLK := inputSignal);

IF fallDetect.Q THEN
(* Falling edge detected — signal just went off *)
offCount := offCount + 1;
END_IF;
InputTypeDescription
CLKBOOLSignal to monitor
OutputTypeDescription
QBOOLTRUE for one scan on falling edge

6. PID Controllers​

6.1 PID — Standard PID Controller​

Proportional-Integral-Derivative feedback controller with anti-windup.

VAR
tempPID : PID;
heaterOutput : REAL;
END_VAR

tempPID(
EN := TRUE,
PV := actualTemp, (* Measured temperature *)
SP := setpointTemp, (* Desired temperature *)
KP := 10.0, (* Proportional gain *)
KI := 0.5, (* Integral gain *)
KD := 2.0, (* Derivative gain *)
CYCLE := 0.1, (* Scan time in seconds *)
MN := 0.0, (* Min output *)
MX := 100.0 (* Max output *)
);

heaterOutput := tempPID.CV;

Inputs:

ParameterTypeDefaultDescription
ENBOOLTRUEEnable
PVREALrequiredProcess variable (measurement)
SPREALrequiredSetpoint (target)
KPREAL1.0Proportional gain
KIREAL0.0Integral gain
KDREAL0.0Derivative gain
CYCLEREAL0.1Scan time in seconds
MNREAL0.0Minimum output
MXREAL100.0Maximum output
MRBOOLFALSEManual reset (clears integral)

Outputs:

ParameterTypeDescription
CVREALControl variable (calculated output)
EREALError (SP - PV)
ERRBOOLTRUE when this call held its output (see Faults)
STATUSDINT0 OK, 1 an input or the result was NaN/±Inf, 2 MN > MX, 3 CYCLE ≤ 0

Algorithm:

Error = SP - PV
P = KP * Error
I = KI * accumulated_integral
D = KD * (Error - prevError) / CYCLE
CV = CLAMP(P + I + D, MN, MX)

No windup, in either direction. When the output is at MN or MX and the integral's next step would push it further, the integral does not move that scan. This is judged on the output, so a reverse-acting loop (negative gains) is protected exactly like a forward one.

Faults: the output holds, never NaN. If an input is NaN or ±Inf (a failed sensor, a bad protocol value), or MN > MX, or CYCLE ≤ 0, the call holds CV and E at their last good values, does not move the integral, and sets ERR with the reason in STATUS. The first good call after that carries on from where it held, with no derivative kick. Validation warns before Download when both limits are literals that cross, or CYCLE is a literal ≤ 0.

loopPID(PV := flowMeter, SP := 120.0, KP := 0.8, KI := 0.3, CYCLE := 0.1, MN := 0.0, MX := 100.0);
valve := loopPID.CV;
IF loopPID.ERR THEN
alarmFlowLoop := TRUE; (* holding: STATUS says why *)
END_IF;

6.2 PIDE — Enhanced PID (Rockwell-Style)​

Extended PID with feed-forward, output bias, manual mode, setpoint limits, and alarm thresholds.

VAR
reactorPID : PIDE;
END_VAR

reactorPID(
EN := TRUE,
PV := reactorTemp,
SP := 180.0,
KP := 5.0,
KI := 0.2,
KD := 1.0,
CYCLE := 0.1,
FF := steamFlow * 0.5, (* Feed-forward from steam *)
BIAS := 10.0, (* Output offset *)
MAXO := 100.0, (* Max output *)
MINO := 0.0, (* Min output *)
MAXS := 200.0, (* Max setpoint *)
MINS := 50.0 (* Min setpoint *)
);

valveOutput := reactorPID.CV;
spClamped := reactorPID.SPH OR reactorPID.SPL;

Additional Inputs (beyond PID):

ParameterTypeDefaultDescription
FFREAL0.0Feed-forward term (added directly to output)
BIASREAL0.0Output bias/offset
MAXOREAL100.0Maximum output
MINOREAL0.0Minimum output
MAXSREAL100.0Maximum setpoint limit
MINSREAL0.0Minimum setpoint limit
MAXIREAL100.0Maximum integral accumulation
MINIREAL-100.0Minimum integral accumulation
DPTSBOOLFALSEDependent gains mode
MOBOOLFALSEManual output mode (CV = MOCV)
MOCVREAL0.0Manual CV value
INIMANBOOLFALSEInitialize integral from MOCV

Additional Outputs:

ParameterTypeDescription
SPHBOOLSetpoint clamped to MAXS
SPLBOOLSetpoint clamped to MINS
ERRBOOLTRUE when this call held its output (as for PID; see PID Faults)
STATUSDINT0 OK, 1 non-finite input or result, 2 crossed limits (output, integral or setpoint), 3 CYCLE ≤ 0

PIDE follows PID's fault rule: a NaN/±Inf input (MOCV included in manual mode), crossed limits or CYCLE ≤ 0 hold CV and set ERR. Dependent gains (DPTS) compute KP·(E + KI·I) + D, so KP = 0 is safe.

Key Differences from PID:

  • Derivative is calculated on PV (not error) to avoid derivative kick on setpoint changes
  • Feed-forward term for measurable disturbance rejection
  • Setpoint clamping with limit flags
  • Manual mode for bumpless transfer between auto and manual
  • Bounded integral accumulation (separate from output limits)

7. TIME Literals​

All timer presets use IEC 61131-3 TIME literals:

LiteralDuration
T#500ms500 milliseconds
T#1s1 second
T#5s5 seconds
T#1m30s1 minute 30 seconds
T#1h1 hour
T#1h30m1 hour 30 minutes
T#2d2 days
T#100ms100 milliseconds
T#10us10 microseconds

8. Complete Example: Pump Station​

A realistic pump control program using timers, counters, edge triggers, and PID.

PROGRAM POU_PumpStation
VAR
(* Inputs *)
startBtn : BOOL;
stopBtn : BOOL;
eStop : BOOL;
levelSensor : REAL; (* 0-100% *)
flowSensor : REAL; (* GPM *)

(* Function block instances *)
runLatch : RS; (* Reset-dominant for safety *)
startDelay : TON; (* Anti-short-cycle delay *)
runTimer : RTO; (* Accumulate total run hours *)
cycleCount : CTU; (* Count start/stop cycles *)
startEdge : R_TRIG; (* Detect start events *)
levelPID : PID; (* Level control *)
dryRunTimer : TON; (* Dry run protection *)

(* Outputs *)
pumpRun : BOOL;
vfdSpeed : REAL;
maintenanceDue : BOOL;
dryRunFault : BOOL;
END_VAR

(* Safety latch — E-stop always wins *)
runLatch(S := startBtn AND NOT dryRunFault, R1 := stopBtn OR eStop);

(* Anti-short-cycle: must wait 30s between starts *)
startDelay(IN := NOT runLatch.Q1, PT := T#30s);
pumpRun := runLatch.Q1 AND startDelay.Q;

(* Count start events *)
startEdge(CLK := pumpRun);
cycleCount(CU := startEdge.Q, PV := 10000, R := FALSE);

(* Accumulate runtime for maintenance scheduling *)
runTimer(IN := pumpRun, PT := T#2000h, R := FALSE);
maintenanceDue := runTimer.Q;

(* Level PID — controls VFD speed *)
levelPID(
EN := pumpRun,
PV := levelSensor,
SP := 75.0, (* Maintain 75% level *)
KP := 5.0,
KI := 0.3,
KD := 0.5,
CYCLE := 0.05, (* 50ms scan *)
MN := 20.0, (* Min speed 20% *)
MX := 100.0 (* Max speed 100% *)
);
vfdSpeed := levelPID.CV;

(* Dry run protection: fault if running with no flow for 10s *)
dryRunTimer(IN := pumpRun AND (flowSensor < 1.0), PT := T#10s);
IF dryRunTimer.Q THEN
dryRunFault := TRUE; (* Latches until operator clears *)
END_IF;

END_PROGRAM

Appendix A: Quick Reference​

Timers​

FBPurposeKey I/O
TONOn-delayIN + PT → Q after delay
TOFOff-delayQ holds TRUE for PT after IN falls
TPPulseFixed-width pulse on rising edge
RTORetentive on-delayAccumulates time, retains on IN=FALSE, needs R to clear

Counters​

FBPurposeKey I/O
CTUCount upCU rising edge → CV++, Q when CV >= PV
CTDCount downCD rising edge → CV--, Q when CV <= 0
CTUDUp/downCU/CD edges, QU (upper), QD (lower)

Bistables​

FBPurposePriority
SRSet-Reset latchSet dominant
RSReset-Set latchReset dominant (use for safety)

Edge Triggers​

FBPurposeOutput
R_TRIGRising edgeQ = TRUE for one scan on FALSE→TRUE
F_TRIGFalling edgeQ = TRUE for one scan on TRUE→FALSE

PID​

FBPurposeKey Features
PIDStandard PIDKP/KI/KD, anti-windup, output clamping
PIDEEnhanced PIDFeed-forward, bias, manual mode, SP limits, alarms

ControlForge v1.0.535 | IEC 61131-3 Function Blocks | Timers, Counters, PID