Findings
What has been measured.
Each finding gives the question it asked, the runtime version it was measured on, the method, the result and where the result stops being true. It opens with what it means on a machine.
-
Measurement · 10 October 2026 · v1.0.1780
Where a soft-PLC's scans wait: a lock census, from 113,972 sync waits to 31
A runtime that serves an IDE, a historian and drivers while it scans can stall its own tasks through shared locks, and on a real-time kernel those stalls can feed on themselves. Counting lock waits, not guessing at them, found the causes, and two of the biggest were not lock code at all.
PLC RuntimeData Logger & Historian -
Measurement · 2 September 2026 · v1.0.1547
A historian forwarder that cost a core: 13 million rows decoded to ship 7 thousand
Store-and-forward from a local history file is the right design, but a forwarder that re-reads more than it sends can quietly take a whole CPU core from the machine. Count rows decoded against rows sent before blaming the decoder.
Data Logger & Historian -
Validation · 27 July 2026 · v1.0.1268
Navier–Stokes in Structured Text: the lid-driven cavity against Ghia, Ghia & Shin (1982)
A PLC language running on a deterministic compute tier can carry real numerical work, and its answers can be checked against published results rather than eyeballed. The same discipline applies to any control calculation: score it against an outside reference.
PLC RuntimeDigital Twin